WS1TC WATER SPECIALIST CLACK TC CONTROL VALVE
Kapaciteti depërtues
m³/h
Rikthimi
%
Maximum TDS
mg/L
Kërkesa për rrjedhje ndikuese
m³/h
Presioni operimit
bar
Konsumi i energjisë
kw
name
mm
WS1TC WATER SPECIALIST CLACK TC CONTROL VALVE
FLOW RATES
Service @ 15 psi/1 bar drop (includes bypass and meter) – 102 lpm (6.12 m3/h) (27 gpm)
Backwash @ 25 psi/1.7 bar drop (includes bypass) – 102 lpm (6.12 m3/h) (27 gpm)
Cv service – 7.0
Cv backwash – 5.4
OPERATING PRESSURES
Minimum/Maximum: 20 – 125 psi (1.4 – 8.6 bar)
OPERATING TEMPERATURES
Minimum/Maximum: 40º – 110º F (4º – 43º C)
DIMENSIONS & WEIGHT
Distributor Pilot – 1.050″ OD Pipe (¾” NPS)
Drain Line – ¾” or 1″ NPT
Brine Line – 3/8″ or ½” OD Poly Tube
Mounting Base – 2 ½”- 8 NPSM
Height From Top Of Tank – 7 3/8″ (187 mm)
Weight – 4.5 lbs (2 kg)
TANK APPLICATIONS
Water Softener: 6″ – 21″ Diameter
Water Filter (1): 6″ – 21″ Diameter
(1) Filter tank size calculated @ 10 gpm of backwash per square foot of bed area / 407 lpm per square meter of bed area.
CYCLES OF OPERATION (Softener Downflow)
1. Backwash 1st (upflow) – 3-12 minutes
2. Regenerate Draw/Slow Rinse (downflow) – 50-70 minutes
3. Backwash 2nd (upflow) – 3-12 minutes
4. Fast Rinse (downflow) – 3-8 minutes
5. Regenerant Refill (in service with treated water) – As programmed
6. Service (downflow)
Options: Backwash Filter, Bypass, Weather Cover
Compatible with the following typical concentrations of regenerants or chemicals: Sodium chloride, potassiumchloride, potassium permanganate, sodium bisulfite, chlorine and chloramines
Copyright © 2023 Ecosoft Albania. All rights reserved.